web site updated 27/08/2010    © Lovekin Ltd 2009-2010    registered in England & Wales No.3950749    2 Ashdene Crescent GU12 6TA

Link to Central Heating Problems and Gas Boiler Problems home page

heating and boiler problems  ~  lovekin.net

home.boilers.other appliances.controls.general problems.who we are.contact us.

Please read our Legal Disclaimer

Baxi Solo 2 PF and Solo 3 PF Gas Boiler Faults, Problems and Fault Finding

Baxi Solo 2 50 PF Boiler Fault (boiler GC No. 41-077-73)

Baxi Solo 2 50 PF boiler won't light. This boiler fault could occur in any of the Baxi Solo 2 PF or Solo 3 PF boilers

Burnt electrical soldered contact on the back of the circuit board from a Baxi Solo 2 50 PF gas central heating boiler. The Baxi Solo 2 PF gas boiler and the Baxi Solo 3 PF gas boiler share a common PCB.

With a demand present for the boiler to fire, this Baxi Solo 2 PF 50 boiler couldn't complete the ignition cycle. The boiler fan would start and stop repeatedly, on a  very short cycle of under one second.

 

This is a fault we've seen before on Baxi Solo PF boilers and is caused by damage to the boiler circuit board (pcb). When we removed the circuit board we found tell-tale damage to one of the soldered contacts of a relay on the circuit board.

Black relay on a Baxi Solo PF boiler circuit board. The same PCB is used on both Baxi Solo 2 and Baxi Solo 3 boilers.

We changed the pcb and the boiler went through a normal ignition cycle, firing up correctly. The same printed circuit board (pcb) is used on the Baxi Solo 2 PF boilers, the Baxi Solo 3 PF boilers and the Baxi Solo 3 PFL boilers.

 

Back to the top

There is no permanent pilot on the Baxi Solo PF boiler ranges so the presence of a pilot on its own indicates a fault state. There are a number of possible causes.

 

If the pilot remains alight when you switch off the electrical power to the boiler there's a fault with the gas valve as the pilot line must close completely when there is no demand for heat.

 

Where the pilot lights during the ignition sequence but the main burner does not light there are still 2 or 3 possible causes.

 

The Baxi Solo boilers we see sometimes struggle to go quickly and cleanly from pilot to main burner because there can be significant disturbance of the pilot flame caused by the fan. This can pull the pilot flame away from the ignition electrodes, making it difficult for the circuit board to sense the presence of the flame by flame rectification. However, these boilers usually manage to light fully within a few seconds.

Legal Disclaimer:

The information provided on this web site  is given in good faith and is only an indication of what we have tried in an effort to resolve heating and boiler problems. You must make your own judgements and we can accept no liability for any damage or injury sustained as a result of trying what we have tried, nor can we accept any liability arising out of misleading, incomplete or incorrect information on this site.

The advertising on this web site is provided by Google and is not controlled by us. We can accept no liability for the content of any advert nor for the outcome of any contact you have with the advertiser or contract you enter into with them.

 

Back to the top

Printed circuit board for Baxi Solo PF boilers. This PCB is used on both Baxi Solo 2 PF and Baxi Solo 3 PF boilers.

Click on an image

for a bigger picture

The burnt electrical contact in the centre of the picture above is one of the pins on the black relay in the picture below

Circuit board for the Baxi Solo 2 PF

Baxi Solo 3 PF and Baxi Solo 3 PFL range of boilers

Baxi Solo 3 60 PF Boiler Fault (boiler GC No. 41-075-07)

Baxi Solo 3 60 PF boiler won't fire up but a pilot is present.

This boiler fault could occur in any of the Baxi Solo 2 PF or Solo 3 PF  or Solo 3 PFL boilers

Ignition electrode and pilot burner on a Baxi Solo 2 PF boiler.

Ignition electrodes on a Baxi Solo PF boiler

Probably the commonest cause of a Solo PF boiler not going from pilot to main burner is a solenoid failure on the gas valve. If a pilot alone is present and you also have 230V between red and blue at the gas valve then the fault should be with the gas valve as the main gas solenoid should open.

 

If the correct voltage is not present between red and blue then either the circuit board is faulty or the wiring connections are faulty or, possibly, the ignition contacts are dirty.

 

Dirty ignition contacts was the fault with our boiler. The high tension spark (HT) jumped easily across the dirty contacts but the very low energy flame-rectification current was unable to pass correctly. We cleaned the contacts up with a very fine file and blew them clean; the ignition then worked normally and the boiler lit.

For more about us see our lovekin.co.uk web site

 

We have also started to put together a guide to shower types, gravity showers and power showers. You can find it at powershowerguide.com

Baxi Solo 2 80 PF Boiler only runs intermittently

This boiler would intermittently fail to run but there was no fixed pattern to the fault

Like all intermittent faults, this fault on a Baxi Solo 2 80 PF boiler was difficult to find. The customer told us that the boiler had been moved some months previously but had worked completely normally for months. Thankfully, the boiler decided to play up while we were there and  the fault persisted long enough for us to check the voltages to the pcb (printed circuit board).

 

We found that we only had between 165 and 175 volts AC between the Permanent Live supply wire and Neutral, indicating a heating fault that was not caused by the boiler. Tracing back along the supply wiring we found a junction box, fitted during the boiler move, where the Permanent Live supply wire had not been clamped under the screw. It simply lay against the screw. Re-making the contact sorted the problem out and the boiler now fires normally on demand.

 

Back to the top

It’s possible that fault-finding may not sort out your problems or that the repair costs mean you should consider having your Baxi boiler replaced. For a replacement boiler or a new boiler installation we would recommend Worcester Bosch. Given current regulations and the work involved, boiler replacement is never cheap but sometimes a new boiler installation is the best option.

Why are Worcester Bosch our first choice for boiler replacement?

Worcester boilers are well made and the quality seems consistently high. Their technical backup is very good. The warranties on Worcester boilers are good and we’ve found that Worcester spares are readily when needed. We hardly ever have to wait long for spares.

And in his spare time Paul is working on a web site about Lake Garda in Italy, particularly Limone sul Garda, Riva del Garda, Malcesine,  Lazise, Bardolino and the town of Garda itself. He's hoping to earn money by carrying advertising on the site from hotels and tour operators, travel companies and other companies linked to the hotel, travel, leisure and tourism sector. The site is PictureLakeGarda.com

Baxi Solo 350 PFL Boiler, pump runs continuously

The pump connected to this boiler ran on indefinitely.

This is a recognised fault that occurs with Solo 2 and Solo 3 boilers.

The circulating pump connected to the Baxi Solo boiler is run from the boiler pcb (circuit board), allowing the pump to be run for a few minutes after a heating demand ends, to remove excess heat from the heat exchanger.

 

In the fault state the boiler continues to send power to the pump indefinitely. The boiler itself fires up and shuts down normally but the fault usually becomes apparent because the householder is disturbed by pump noise during the night.

 

The fault can only be resolved by changing the Baxi Solo circuit board.

 

Back to the top